Article specifications
| Part no. | 38519 |
|---|---|
| Item description | NSHXAFÖ 1,8/3 kV black 1 x 4 mm² |
| AWG, approx. | 12 |
| Copper factor per km | 38,0 |
| Weight, approx. (kg/km) | 95,0 |
| Reaction to fire class | Eca |
| Metres per packaging unit | 100, 500, 1000 |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892258404 |
| Customs tariff number | 85446010 |
Manufacturer technical information
Rubber sheathed single core cable acc. to E DIN VDE 0250-606
Temperature range
flexible -25°C to +70°C
fixed -40°C to +90°C
fixed -40°C to +90°C
Permissible operating temperature of the conductor
+90°C
Nominal voltage
AC U0/U 1800/3000 V
Max. permissible operating voltage
alternating current (AC) conductor/earth 2100 V
three-phase alternating current (AC) conductor/conductor 3600 V
direct current (DC) conductor/earth 2700 V
direct current (DC) conductor/conductor 5400 V
three-phase alternating current (AC) conductor/conductor 3600 V
direct current (DC) conductor/earth 2700 V
direct current (DC) conductor/conductor 5400 V
Test voltage
6000 V
Minimum bending radius
flexible 10x Outer-Ø
fixed 6x Outer-Ø
fixed 6x Outer-Ø
Cable Structure
- Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: rubber (EPR) acc. to DIN VDE 0207-20 (compound type 3GI3)
- x = without protective conductor
- Outer cladding: halogen-free polymer acc. to DIN VDE 0207-24 (compound type HM3)
- Colour: black
Properties
- resistant to: oil
- halogen-free
Tests
- corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
- oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- For use in rail vehicles and buses, as well as in dry rooms. The cable is short-circuit and earth-fault proof in switchgear and distribution boards up to 1000 V. Normative permissible laying types are: in pipes, closed installation ducts, for connecting moving parts, device wiring and bundled. Not for use on cable ladders and cable trays.



Reviews