Article specifications
| Part no. | 10900 |
|---|---|
| Item description | Single 600-O black 1 x 150 mm² |
| AWG, approx. | 250 kcmil |
| Outer diameter, approx. (mm) | 25 |
| Copper factor per km | 1440,0 |
| Weight, approx. (kg/km) | 1750,0 |
| Metres per packaging unit | 500, 1000 |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892172533 |
| Customs tariff number | 85444995 |
Manufacturer technical information
PVC sheathed single core cable acc. to UL-Std. 758 (AWM) Style 10107, CSA-Std. C22.2 No. 210 - AWM I/II A/B, in alignment with DIN VDE 0285-525-2-31 / DIN EN 50525-2-31
Temperature range
flexible -5°C to +90°C
fixed -40°C to +90°C
fixed -40°C to +90°C
Permissible operating temperature of the conductor
+90°C
Nominal voltage
VDE AC U0/U 600/1000 V
UL (AWM) AC 600 V
UL (AWM) AC 600 V
Test voltage
4000 V
Breakdown voltage
8000 V
Minimum bending radius
flexible 7.5x Outer-Ø
fixed 4x Outer-Ø
fixed 4x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: Special-PVC acc. to UL-Std. 1581
- Core identification: see datasheet
- G = with protective conductor GN-YE,
- x = without protective conductor
- Outer sheath: PVC acc. to DIN VDE 0207-5 (compound type YM5), UL-Std. 1581
- Sheath colour: black (RAL 9005)
- Length marking: in metres
Properties
- resistant to: UV radiation
- largely resistant to: oil,
- for details, see "Technical Information"
- for outdoor use
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2, UL VW-1, CSA FT1
- certifications and approvals:
- EAC
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- PVC sheathed single core cable suitable for medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, as well as outdoors. May not be laid directly in soil or water. This two-standard sheathed single core cables are preferably used in export-oriented mechanical engineering on machine tools, production lines and in plant construction.





Reviews