Article specifications
| Part no. | 36005 |
|---|---|
| Item description | 05RN-F black 3 G 1,5 mm² |
| AWG, approx. | 16 |
| Outer diameter, approx. (mm) | 8,6 - 11,0 |
| Copper factor per km | 43,0 |
| Weight, approx. (kg/km) | 157,0 |
| Reaction to fire class | Eca |
| Metres per packaging unit | 100, 500, 1000 |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892168215 |
| Customs tariff number | 85444995 |
Manufacturer technical information
Rubber connection cable, H05RN-F acc. to DIN VDE 0285-525-2-21 / DIN EN 50525-2-21; 05RN-F in alignment with DIN VDE 0285-525-2-21 / DIN EN 50525-2-21
Temperature range
flexible -25°C to +60°C
fixed -30°C to +60°C
fixed -30°C to +60°C
Permissible operating temperature of the conductor
+60°C
Nominal voltage
AC U0/U 300/500 V
Max. permissible operating voltage
alternating current (AC) conductor/earth 318 V
three-phase alternating current (AC) conductor/conductor 550 V
direct current (DC) conductor/earth 413 V
direct current (DC) conductor/conductor 825 V
three-phase alternating current (AC) conductor/conductor 550 V
direct current (DC) conductor/earth 413 V
direct current (DC) conductor/conductor 825 V
Test voltage core/core
2000 V
Minimum bending radius
7.5x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: rubber acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI4)
- Core identification acc. to DIN VDE 0293-308, colour coded
- Protective conductor: starting with 3 cores,
- G = with protective conductor GN-YE,
- x = without protective conductor
- Cores stranded with optimal lay lengths
- Outer sheath: rubber acc. to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (compound type EM2)
- Sheath colour: black
Properties
- resistant to: weathering effects
- for outdoor use
Tests
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- certifications and approvals:
- H05RN-F: HAR
- H05RN-F: EAC
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- Connection cable for use in dry, damp and wet rooms as well as outdoors; for connecting appliances in households, kitchens or offices involving light mechanical stress (e.g. hoovers, kitchen appliances and other portable household and garden equipment)




Reviews