Article specifications
| Part no. | 52878 |
|---|---|
| Item description | H05Z-K grey 1 x 0,5 mm² |
| Core colour | grey |
| AWG, approx. | 20 |
| Outer diameter, approx. (mm) | 2,1 - 2,6 |
| Copper factor per km | 4,8 |
| Weight, approx. (kg/km) | 9,0 |
| Reaction to fire class | Eca |
| Metres per packaging unit | 100 |
| Custom cut lengths available | no |
| EAN / GTIN | 4060892222061 |
| Customs tariff number | 85444995 |
Manufacturer technical information
Single core acc. to DIN VDE 0285-525-3-41 / DIN EN 50525-3-41
Temperature range
flexible -5°C to +90°C
fixed -40°C to +90°C
fixed -40°C to +90°C
Permissible operating temperature of the conductor
+90°C
Nominal voltage
AC U0/U 300/500 V
Test voltage
2000 V
Minimum bending radius
fixed 4x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Foil wrapping around conductor permissible
- Core insulation: cross-linked polyolefin acc. to DIN VDE 0207-363-5 / DIN EN 50363-5 (compound type EI5)
- Core identification: see datasheet
Properties
- resistant to: ozone
- halogen-free
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
- halogen-free acc. to DIN VDE 0285-525-1 / DIN EN 50525-1 Appendix B
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
- ozone-resistant acc. to DIN VDE 0473-811-403 / DIN EN 60811-403
- certifications and approvals:
- HAR
- EAC
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- For applications that require a low development of smoke and corrosive gases in case of fire. Used for internal wiring of devices and for connecting luminaires. For installation in electrical pipes on and under plaster; but only for signal and control circuits.





Reviews