Article specifications
| Part no. | 11027264 |
|---|---|
| Item description | HELUPOWER® SOLARFLEX®-X PREMIUM red 1 x 2,5 mm² |
| Sheath colour | red |
| AWG, approx. | 14 |
| Outer diameter, approx. (mm) | 4,8 - 5,4 |
| Copper factor per km | 24,0 |
| Weight, approx. (kg/km) | 44,0 |
| Metres per packaging unit | - |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892542619 |
| Customs tariff number | 85446010 |
Manufacturer technical information
Cross-linked single core cable acc. to DIN VDE 0283-618 / DIN EN 50618, IEC 62930, TÜV Rheinland 2 PfG 2750
Temperature range
flexible -25°C to +60°C
fixed -40°C to +90°C
fixed -40°C to +90°C
Permissible operating temperature of the conductor
+120°C
Short circuit temperature at the conductor
+250°C (Short circuit duration max. 5 s)
Nominal voltage
AC U0/U 1000/1000 V
DC U0/U 1500/1500 V
DC U0/U 1500/1500 V
Test voltage
6500 V
Minimum bending radius
flexible 6x Outer-Ø
fixed 4x Outer-Ø
fixed 4x Outer-Ø
Cable Structure
- Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: cross-linked compound
- x = without protective conductor
- Outer sheath: cross-linked compound
- Sheath colour: see datasheet
Properties
- resistant to: UV radiation, ozone, weathering effects, water
- for outdoor use
- direct burial
- halogen-free
- for permanent installation in fresh water up to 1m water depth (AD8)
Tests
- halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
- UV-resistant acc. to DIN VDE 0283-618 / DIN EN 50618 Appendix E
- ozone-resistant acc. to DIN VDE 0283-618 / DIN EN 50618
- weather-resistant acc. to DIN VDE 0283-618 / DIN EN 50618 Appendix E
- Current carrying capacity acc. to DIN VDE 0283-618 / DIN EN 50618
- Short-circuit and earth-fault proof acc. to DIN VDE 0100-520 / HD 60364-5-52
- DC Voltage resistance of the insulation acc. to DIN VDE 0283-618 / DIN EN 50618 Tab. 2
- Improved water resistance acc. to TÜV Rheinland 2 PfG 2750
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
- the installation instructions must be observed
Application
- HELUPOWER® SOLARFLEX®-X PREMIUM is suitable for permanent installation in fresh water (up to 1 metre water depth) and is used for wiring photovoltaic modules in floating solar parks. A wide range of applications in different countries is possible due to EN 50618 and IEC 62930 certification. Suitable for direct burial. The maximum DC voltage of the system in which the cable is installed must not exceed 1.8 kV. The cable is suitable for use in and on devices and systems with protective insulation (protection class II).