Article specifications
| Part no. | 11973 |
|---|---|
| Item description | JB-750 HMH grey 5 G 4 mm² |
| AWG, approx. | 12 |
| Outer diameter, approx. (mm) | 13,4 |
| Copper factor per km | 192,0 |
| Weight, approx. (kg/km) | 357,0 |
| Reaction to fire class | Dca |
| Metres per packaging unit | 500, 1000 |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892049743 |
| Customs tariff number | 85444995 |
Manufacturer technical information
Control and connection cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51, DIN VDE 0285-525-3-11 / DIN EN 50525-3-11
Temperature range
flexible -15°C to +70°C
fixed -40°C to +70°C
fixed -40°C to +70°C
Nominal voltage
AC U0/U 450/750 V
Test voltage core/core
4000 V
Minimum bending radius
flexible 12.5x Outer-Ø
fixed 4x Outer-Ø
fixed 4x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: halogen-free polymer acc. to DIN VDE 0207-363-7 / DIN EN 50363-7 (compound type TI6)
- Core identification acc. to DIN VDE 0293-308, colour coded
- G = with protective conductor GN-YE
- Cores stranded with optimal lay lengths
- Outer sheath: halogen-free polymer acc. to DIN VDE 0207-363-8 / DIN EN 50363-8 (compound type TM7)
- Sheath colour: grey (RAL 7001)
- Length marking: in metres
Properties
- largely resistant to: oil
- halogen-free
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
- halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
- corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
- Control and connection cable for use on machine tools, conveyor belts, production lines, in plant engineering, in air conditioning technology, in metallurgical plants and steel rolling mills. For fixed installation or flexible applications involving medium mechanical stress and occasional, non-recurring free movement without forced movement guidance and without tensile stress. Suitable for use in dry, damp and wet rooms and on plaster.



Reviews