Benefits
- Possible to operate at higher peak temperature (almost 30% more) compared to conventional PVC cables
Applications
- For connection of motors, transformers, reels, plants, machines, appliances, switch cabinets and other installations with a higher operating or ambient temperature
- For indoor and outdoor use
Technical specifications
General information
| Brand | ÖLFLEX® |
|---|---|
| Product type | Power and control cable |
| Weight | 74 kg/km |
| Copper index | 29 kg/km |
| Industry segment | HVAC |
| customs code | 85444995 |
Electrical parameters
| Nominal voltage | U0/U: 300/500 V AC rms according to IEC |
|---|---|
| Test voltage | 2.5 kV |
| Max. conductor resistance at 20°C | 19.5 Ω/km |
| Conductor/conductor operating capacitance (800Hz), approx. | 94 nF/km |
| Inductance (800 Hz), approx. | 0.739 mH/km |
Product design
| Cable dimensions | 3G1 |
|---|---|
| Nominal conductor cross-section (metric) | 1 mm² |
| Conductor material | Bare copper |
| Conductor design | IEC 60228 class 5: fine-wire |
| Including protective earth | Yes |
| Number of cores | 3 |
| Stranding type | Layered stranding |
| Nominal outer diameter | 6.9 mm |
| Cable shape | Round |
| Core insulation basic material | Polyvinylchloride |
| Core insulation basic material, short form | PVC |
| Basic material of outer sheath | Polyvinylchloride |
| Basic material of outer sheath, short form | PVC |
| Outer sheath colour | black |
| Cable sheath RAL colour | RAL 9005 |
| Core identification | Colours |
| Conductor colour code | VDE 0293-308 |
Product features
| Application area | Flexible; Fixed installation |
|---|---|
| Minimum bending radius, stationary | 4 x outer diameter |
| Minimum bending radius in mm, fixed installation | 27.6 mm |
| Minimum bending radius, occasionally flexing | 15 x outer diameter |
| Minimum bending radius in mm, occasionally flexing | 103.5 mm |
| Temperature, fixed installation | -20 °C to 90 °C max. conductor temperature |
| Temperature, fixed installation max | 90 °C |
| Temperature, fixed installation min | -20 °C |
| max. conductor temperature, occasionally moved | 5 °C to 90 °C max. conductor temperature |
| Temperature, occasionally moved max | 90 °C |
| Temperature, occasionally moved min | 5 °C |
| Max. short-term temperature | 105 °C |
| Flame-retardant | Yes |
| Flame retardance according to | IEC 60332-1-2 |
| UV-resistant | Yes |
| UV-resistant according to | EN 50525-1 (cables with a black sheath are suitable for permanent outdoor use) |
| Halogen-free | No |
| Oil-resistant | No |
| PWIS-free | Yes |
| PWIS-free according to | VDMA 24364-B2-L |
Certifications and standards
| CE marking | Yes |
|---|---|
| EAC-certified | Yes |
| EAC certification number | ЕАЭС N RU Д-DE.АЮ64.В.00130/20 |
| VDE certified | No |
| Flame retardance tested according to UN/ECE-R118 | No |
Datasheets and certificates
- Data sheet: DB0026001EN.pdf
- Technical table: T9_Core ID code as per VDE colour code_int.pdf
- CE declaration of conformity: CE0026001EN.pdf
- CPR declaration of performance: UILCPRDOP18_0026001-1EN.pdf
Manufacturer notes
- Inductance and operating capacitance are neither defined nor controlled electrical parameters. The specified values were determined by calculation and may deviate due to tolerances.
- Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
- Photographs and graphics are not to scale and do not represent detailed images of the respective products.
- The absence of PWIS raw materials does not protect against the potential risk of contamination with substances that interfere with the paint wetting during subsequent handling of the product(s) during transport, storage or further processing after delivery.
LAPP product information and documents
Manufacturer nominal values; images are representative. The confirmed configuration, quantity and displayed total apply to the order.





Reviews