Cable gland; M 32; Clamping range (min./max.): 9 – 15 mm; Spanner size 1: 36; blue; Polyamide Uncoated; IP 68 – 10 bar (30 min), IP 66; For use in hazardous areas
Benefits
- Cold impact resistance
- High strain relief
- Wide, variable clamping ranges
Applications
- Equipment group II / Category 2G+1D
- For mobile applications in offshore and marine industries
- Chemical and petrochemical industry
Technical specifications
General information
| Brand | SKINTOP® |
|---|---|
| Product type | Cable gland |
| Delivery with lock nut | No |
| Delivery with O-ring | Yes |
| Weight | 0.026 kg |
| Packaging type | Bag |
| Delivery Unit | 25 |
| Installation type | in threaded borehole |
| customs code | 39269097 |
Product design
| For armoured cables | No |
|---|---|
| Glass fibre-reinforced | No |
| Number of cable entries | 1 pc. |
| With bending protection | No |
| Cable gland design | Straight |
| Total length | 47 mm |
| Clear width | 21 mm |
| Thread type | Metric |
| Thread size | M 32 |
| Thread increase | 1,5 |
| Thread length | 10 mm |
| Thread standard | DIN EN 60423 |
| Spanner size 1 | 36 mm |
| Spanner size 2 | 36 mm |
| Hexagon corner dimensions | 40.3 mm |
| Min. clamping range | 9 mm |
| Max. clamping range | 15 mm |
| EMC shielding | No |
| Seal type | Conduit sealing ring |
| O-ring material | Acrylonitrile butadiene rubber |
| O-ring material, short form | NBR |
| Sealing material | Chloroprene rubber |
| Body material | Polyamide |
| Body material, short form | PA |
| Surface protection | Uncoated |
| Colour | blue |
| RAL colour | RAL 5015 |
Product features
| IP protection rating | IP 68 – 10 bar (30 min); IP 66 |
|---|---|
| For use in hazardous areas | Yes |
| Temperature (min.) | -20 °C |
| Temperature (max.) | 80 °C |
| Flame-retardant | No |
| UV-resistant | No |
| Chemical resistant | Yes |
| Acid-resistant | No |
| Halogen-free | No |
| Oil-resistant | Yes |
| Impact-resistant | Yes |
| Vibration protection | Yes |
| Strain relief | Yes |
Certifications and standards
| CE marking | Yes |
|---|---|
| UL recognized | No |
| UL listed | No |
| cUR recognised | No |
| cUL listed | No |
| CSA certified | No |
| VDE certified | No |
| ATEX certification | IECEx IBE 13.0027X : Ex II 2G Ex eb IIC Ex II 1D Ex ta IIIC |
| CCCex certified | Yes |
| For Ex zone gas | 1, 2 |
| For Ex-zone dust | 20, 21, 22 |
| GGVS certified | No |
| DNV-certified | Yes |
| DNV certificate number | TAE00002NW |
| Fire protection tested for railway vehicles | No |
| Ecolab certified | No |
| NSF certified | No |
| FDA certified | No |
| EHEDG certified | No |
Datasheets and certificates
- Data sheet: DB54115400EN.pdf
- Assembly instructions: BZ99090101DE_EN.pdf
- Data and operating instructions: DM54115205DE_EN.pdf
- Atex approval: ZA54115200EN.pdf
- DNV approval: ZN54115200EN.pdf
- Technical table: T21_Thread dimensions for cable glands_int.pdf
- Technical table: T22_Protection ratings to DIN EN 60529_int.pdf
- Technical table: T23_Cable glands_int.pdf
- Selection table: A8_Cable entries at a glance.pdf
- Installation notes: MH54115400DE_EN.pdf
- CE declaration of conformity: CE54115200EN.pdf
- CCC-ATEX certificate: AC54115200EN.pdf
Manufacturer notes
- Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
- Photographs and graphics are not to scale and do not represent detailed images of the respective products.
LAPP product information and documents
Manufacturer nominal values; images are representative. The confirmed configuration, quantity and displayed total apply to the order.






Reviews
There are no reviews yet.