Article specifications
| Part no. | 14002 |
|---|---|
| Item description | OZ-BL blue 3 x 0,75 mm² |
| AWG, approx. | 19 |
| Outer diameter, approx. (mm) | 5,6 |
| Copper factor per km | 21,6 |
| Weight, approx. (kg/km) | 54,0 |
| Reaction to fire class | Eca |
| Metres per packaging unit | 100, 500, 1000 |
| Custom cut lengths available | yes |
| EAN / GTIN | 4060892010255 |
| Customs tariff number | 85444995 |
Manufacturer technical information
PVC control cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
Temperature range
flexible -15°C to +80°C
fixed -40°C to +80°C
fixed -40°C to +80°C
Nominal voltage
AC U0/U 300/500 V
Test voltage core/core
3000 V
Breakdown voltage
6000 V
Mutual capacitance core/core
at 800 Hz, approx. 120 pF/m
Inductance
approx. 0.68 mH/km
Minimum bending radius
flexible 7.5x Outer-Ø
fixed 4x Outer-Ø
fixed 4x Outer-Ø
Cable Structure
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: PVC, compound type Z 7225
- Core identification acc. to DIN VDE 0293-334, black cores with consecutive labeling in white digits
- x = without protective conductor (OZ)
- Cores stranded in layers with optimal lay lengths
- Outer sheath: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
- Sheath colour: blue (RAL 5015)
- Length marking: in metres
Properties
- resistant to: UV radiation, weathering effects
- largely resistant to: oil,
- for details, see "Technical Information"
- for outdoor use
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- UV-resistant acc. to DIN EN ISO 4892-2
- weather-resistant acc. to DIN EN ISO 4892-2
- certifications and approvals:
- EAC
- VDE-Reg.-No. 7032, valid for temperature range up to +70°C
Notes
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
- with blue sheathing for the installation of intrinsically safe systems (ignition protection type -i-) in explosion-endangered areas according to DIN VDE 0165-1 / DIN EN 60079-14 / IEC 60079-14, Section 16.2.2
Application
- Used for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control. For explosion-endangered areas marked as intrinsically safe (blue) (ignition protection type -i-) flexible control or measurement cable for intrinsically safe systems in measurement and control technology. These systems are not earthed and have a separate power circuit. These cables are not suitable for burial in the ground.