FLAME-JZ-CH FRNC 4G35 – 300/500 V, GREY RAL 7001
Manufacturer article number: 1003072 · TKD
Article specifications
| Variant | FLAME-JZ/OZ-CH FRNC |
|---|---|
| Dimension | 4 G 35 |
| Outer-Ø [mm] nom. | 29,8 |
| Cu Index [kg/km] | 1,690.0 |
| Weight [kg/1.000] | 2,264.0 |
Series information: FLAME-JZ/OZ-CH FRNC – Dca
Application
halogen-free and environmentally power, control and connecting cable in electrical facilities, in fire vulnerable areas and facilities with high concentration of people and property values, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
SPECIAL FEATURES
- LABS-free (during production)
- FRNC (Flame Retardant, Non Corrosive)
- LSF 0H ( Low smoke in fume, zero halogen)
- recommended for EMC-applications
REMARKS
- RoHS compliant
- compliant with 2014/35/EU Directive (“Low Voltage Directive“) CE
- Alternatively available: FLAME-JZ-CHö FRNC with increased oil resistance
- Special versions, other dimensions, cross-sections, core and sheath colors are available on request
DESIGN
| Conductor material | bare copper strand |
|---|---|
| Conductor class | acc. to IEC 60228 cl. 5 |
| Core insulation | special halogen-free compound |
| Core identification | acc. to DIN VDE 0293 black cores with white numerals with GNYE from 3 cores |
| Stranding | stranded in layers |
| Overall shield | copper braid tinned; coverage approx. 85 % |
| Outer sheath material | special halogen-free compound |
| Sheath colour | grey, RAL 7001 |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | Uo/U: 300/500 V |
|---|---|
| Testing voltage | 3 kV |
| Conductor resistance | acc. to IEC 60228 cl. 5 |
| Insulation resistance | min. 20 MΩ x km |
| Current carrying capacity | acc. to DIN VDE, see technical Guidelines |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | 6 x d |
|---|---|
| Min. bending radius moved | 15 x d |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40 °C / +70 °C |
|---|---|
| Operat. temp. moved min/max [°C] | – 5 °C / +70 °C |
PROPERTIES IN CASE OF FIRE
| Halogen-free | halogen-free acc. to IEC 60754-1 |
|---|---|
| Smoke density | acc. to IEC 61034-1 and IEC 61034-2 |
| Corrodibility | acc. to IEC 60754-2 |
| Burning behavior | halogen-free and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 Kat. C |
Manufacturer documents
Series illustration. Dimensions and execution follow the article specifications.




Reviews