EIB/KNX BUS (ST)-PVC Eca 2X2X0,8 – GREEN
Manufacturer article number: 2003702 · TKD
Article specifications
| Variant | EIB/KNX BUS PVC |
|---|---|
| Type | (St)-PVC – GN |
| Dimension | 2 X 2 X 0,8 |
| Outer-Ø [mm] nom. | 6,2 |
| Cu Index [kg/km] | 22.0 |
| Weight [kg/1.000] | 64.0 |
Series information: EIB/KNX BUS 75 Ohm
Application
as a buscable for EIB/KNX systems, in the field of intelligent building automation (e.g. motion detectors, lighting, heating / air conditioning / ventilation, time recording systems, blinds, etc.) as well as measuring and control cable in power installations.
Suitable for fixed installation on and under plaster and in pipes and cable ducts, in dry, damp and wet rooms but not outdoors without UV protection.
Standard acc.to KNX-Spec.: EN 50090-2-1 & EN 50090-2-2
SPECIAL FEATURES
- TKD EIB/KNX cables are testet with increased testing voltage (4 kV)
The cables can be layed without restrictions next powercables or touch them.
- YCYM – standard description in Germany for so-called EIB/KNX cable with
high voltage test 4kV and corresponds to our type: EIB/KNX BUS (St)-PVC - EMC compliant shielding
REMARKS
- RoHS-compliant
- LABS/silicone-free (during production)
- compliant with 2014/35/EU Directive (“Low Voltage Directive“) CE
- FRNC: Flame Retardant Non Corrosive, halogen-free
- EIB/KNX – the KNX building system was originally called „European Installation Bus“ (abbreviated to EIB)
DESIGN
| Conductor material | bare copper wire |
|---|---|
| Conductor class | Ø 0,8 mm: single-wire |
| Core insulation | PVC resp. halogen-free compound |
| Core identification | red-black, white-yellow |
| Stranding | cores twisted to quad |
| Overall shield | alu-lamin. polyester foil, with subjacent tinned drain wire |
| Outer sheath material | PVC resp. halogen-free compound |
| Sheath colour | green RAL 6018 (GN) |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | 300 V (not for high voltage purposes) |
|---|---|
| Testing voltage | core/sheath: 4 kV |
| Loop resistance | max. 73,2 Ω/km |
| Insulation resistance | min. 100 MΩ x km |
| Capacity | max. 100 nF/km |
| Characteristic impedance | nom. 75 Ω/km |
| Coupling | max. 200 pF/km |
PROPERTIES IN CASE OF FIRE
| Halogen-free | acc. to IEC 60754-1 (FRNC Typen) |
|---|---|
| Burning behavior | flame retardant acc. to IEC 60332-1-2 |
Manufacturer documents